FM-200 vs Novec 1230 vs inert gas vs CO2: choosing a clean agent in Saudi Arabia after Kigali

FM-200 (HFC-227ea) is under a gradual phase-down in Saudi Arabia through the Kigali Amendment: an HFC freeze from 2028 and an 85% cut by 2047, which does not mean existing systems must stop.

3M ended Novec 1230 manufacturing at the end of 2025 and the same agent (FK-5-1-12) continues from other makers, so new projects now compare FM-200, FK-5-1-12 and inert gas, with CO2 kept for normally unoccupied rooms.

What we deliver

  • Agent selection for each room: FM-200, FK-5-1-12, inert gas or CO2, based on occupancy, room size and hazard.
  • System design and agent quantity calculations by our in-house engineering team to NFPA 2001 and ISO 14520.
  • Supply and installation of FM-200 and clean-agent systems from several international brands, in Riyadh and across Saudi Arabia.
  • Replacement of old Halon systems and older FM-200 systems.
  • Room integrity (door fan) testing before handover.
  • Maintenance contracts, and cylinder refills for the systems we supply and install.

Request an FM-200 quotation

Only name and mobile are required.

Send files (BOQ, drawings) later to info@tals.sa or WhatsApp.

Prefer to talk first?

Projects line

055 544 3168

📞 Call

info@tals.sa

The official requirement

«نظام الهالون أو بدائله: هو عبارة عن شبكة أنابيب موزعة على الأماكن المطلوب حمايتها تغذى من اسطوانات تحتوي على غاز الهالون أو بدائله (كوسيط إطفاء) محفوظا تحت ضغط النيتروجين … علما بأن نظام الهالون في طريقة للحظر دوليا لتأثيره على البيئة، وسـيحل محله مواد بديلة للهالون.»

Civil Defense defines a halon or halon-alternative system as a pipe network fed from cylinders pressurised with nitrogen, and notes that halon is being phased out internationally and replaced by alternative agents.

Source: Saudi Civil Defense, «أنظمة مكافحة الحريق وأنظمة الإنذار» (Fire-fighting and alarm systems), item 2-7/3/2

«تشمل أنظمة الإطفاء نظام الرش الآلي بالإضافة إلى أنظمة إطفاء الحريق البديلة والتي تشمل ما يلي: … 4. أنظمة ثاني أكسيد الكربون (904.8) 5. أنظمة الهالون (904.9) 6. الأنظمة النظيفة (904.10) 7. أنظمة الرذاذ الضبابي (904.11)»

The Civil Defense building guides list CO2 (SBC 801 §904.8), halon (§904.9) and clean-agent systems (§904.10) as recognised alternative extinguishing systems.

Source: Civil Defense, Educational Buildings Guide, Group (E), p.26

The Civil Defense regulations we read do not name FM-200 or Novec. They speak of halon alternatives and clean systems; the agent is fixed in the approved design.

Comparison table

"—" means we have no read source for a figure; the designer sets it from the manufacturer's data.

FM-200Novec 1230 / FK-5-1-12Inert gas (IG-541 etc.)CO2
Chemical nameHFC-227ea (FM-200 is a Chemours trademark)FK-5-1-12IG-541: 52% nitrogen, 40% argon, 8% CO2; also IG-01, IG-55, IG-100Carbon dioxide
StandardISO 14520 part 9; NFPA 2001ISO 14520 part 5; NFPA 2001ISO 14520 parts 12–15NFPA 12
How fastExtinguishing level in 10 seconds or less (manufacturer)—Lowers oxygen; design concentration in about 60 seconds, typically—
Occupied roomsSuitable for occupied spaces (manufacturer); NOAEL 9%——Normally unoccupied rooms
Effect on equipmentElectrically non-conductive, leaves no residue (manufacturer)———
EnvironmentODP 0; GWP 3220 (100-year); 34.2 years in the atmosphereWithin the broad PFAS definitionNot an HFC—
Status after 2025Kigali controlled substance; KSA freeze 2028, 85% cut by 20473M manufacturing ended end-2025; same agent from other makers—Named by the hotels regulation for electrical, generator and transformer rooms
Room needsTight room to hold concentrationTight room to hold concentrationMore cylinders, more storage space, pressure-relief venting—

How to choose for your room

  • Server rooms and data centres: the information-centres regulation asks for «الغازات المغمده المناسبه التي لا تحدث تلفيات بالمكان» (suitable flooding gases that do not damage the place) and names no agent. The usual choice is FM-200 or FK-5-1-12 for small and medium rooms, and inert gas for large halls.
  • Electrical, generator and transformer rooms: the hotels regulation names CO2 for these rooms. Where technicians enter often, an alternative is studied in the design, and the design needs Civil Defense approval before work starts.
  • Existing Novec 1230 system: FK-5-1-12 is still made by other manufacturers; the US Fire Suppression Systems Association advises confirming the replacement agent with the system's manufacturer.
  • Existing FM-200 system: Kigali steps down HFC supply over time, so plan agent availability for refills with your supplier over the system's life.

Questions procurement teams ask

Is FM-200 still allowed in Saudi Arabia after the Kigali Amendment?

Yes. Kigali is a phase-down of HFCs, not a ban. Saudi Arabia ratified it on 10 September 2025; the HFC freeze starts in 2028, with an 85% cut by 2047.

Has Novec 1230 been discontinued, and what replaces my system's agent?

3M's annual report filed in February 2026 says it completed its exit from PFAS manufacturing at the end of 2025, which covers Novec 1230. The same agent, FK-5-1-12, is made by other manufacturers; confirm the replacement with your system's manufacturer.

Is FM-200 safe for people in the room?

The manufacturer describes it as suitable for occupied spaces, and its no-observed-adverse-effect level (NOAEL) is 9%. The design concentration for each room is set to NFPA 2001.

What is the difference between FM-200 and inert gas?

FM-200 reaches extinguishing level in 10 seconds or less (manufacturer data); inert gas works by lowering oxygen and typically takes about 60 seconds. Inert gas needs more cylinders and pressure-relief venting.

Does Civil Defense require FM-200 by name?

The regulations we read do not name FM-200 or Novec. The information-centres regulation (article 14/1) asks for automatic extinguishing «بإستخدام غاز الهالون أو الغازات المغمده المناسبه التي لا تحدث تلفيات بالمكان».

Why is CO2 named for electrical rooms?

The hotels regulation requires electrical, generator and transformer rooms to have «نظام الإطفاء الآلي باستخدام غاز ثاني أكسيد الكربون» (automatic CO2 extinguishing). CO2 total flooding is used in normally unoccupied rooms.