Gas fire suppression for electrical, UPS and generator rooms in Riyadh: CO2 or FM-200
The Civil Defense hotels regulation names carbon dioxide (CO2) for electrical, generator and transformer rooms, while rooms that staff enter often can be designed with a clean agent such as FM-200, subject to the approved design.
TALS supplies and installs gas suppression for these rooms in Riyadh and across Saudi Arabia, choosing the right agent for each room.
What we deliver
- Supply and installation of gas suppression: CO2, FM-200 or another clean agent, from multiple international brands.
- A room-by-room review: occupied or unoccupied, and what equipment it holds.
- Design and agent quantity calculations by our in-house engineering team (NFPA 2001 / ISO 14520 for clean agents).
- Detection, control and release panel, linked to the fire alarm and HVAC shutdown.
- Room integrity (door fan) test for clean-agent rooms.
- Maintenance contracts, and cylinder refills for our own projects.
- Replacement of old Halon and old FM-200 systems.
The official requirement
«ت- تجهز الغرف الكهربائية وغرف المولدات والمحولات بنظام الإطفاء الآلي باستخدام غاز ثاني أكسيد الكربون»"Electrical rooms, generator rooms and transformer rooms shall be fitted with an automatic extinguishing system using carbon dioxide gas."
Sector specifics
- Typical rooms: electrical and switchgear rooms, control and relay rooms, UPS and battery rooms, generator rooms, transformer rooms.
- CO2 for unoccupied rooms: this is the agent the regulation names for electrical, generator and transformer rooms. It is not used at flooding concentration while people are in the room, so it needs lock-out during maintenance, a pre-discharge alarm, a time delay and warning signs.
- Clean agent for rooms staff enter: FM-200 (HFC-227ea) or FK-5-1-12 for switchgear, control and UPS rooms inside occupied buildings. The manufacturer describes FM-200 as safe for occupied spaces within NFPA 2001 limits; it is non-conductive and leaves no residue. Any change from the named agent needs Civil Defense approval of the design before work starts.
- Room separation: the hotels and information-centre regulations require generator and transformer rooms to be well isolated from the rest of the building, and that separation also helps the room hold the gas.
Questions procurement teams ask
Which agent does Civil Defense name for electrical rooms?
The hotels regulation names carbon dioxide for electrical, generator and transformer rooms (Section 11/6/t, p.19); an earlier clause allows CO2 or halon linked to the automatic alarm (p.14, item 11).
Can FM-200 be used instead of CO2?
Clean-agent systems are listed in the Saudi Building Code (SBC 801, section 904.10), as cited in Civil Defense building guides. Choosing an agent other than the one named needs Civil Defense approval of the drawings before work.
Why is CO2 unsuitable for rooms staff enter?
CO2 at flooding concentration is not used with people present, so it needs lock-out and a delay before discharge. FM-200 is designed for occupied spaces within NFPA 2001 limits, according to manufacturer data.
Must the electrical room be separated from the building?
Yes in hotels and information centres: both regulations require electrical installation, generator and transformer rooms to be well isolated from the rest of the building and away from escape routes.
Do you cover electrical rooms outside Riyadh?
Yes. We supply and install gas suppression for electrical, UPS and generator rooms in Riyadh and across Saudi Arabia.